Code Compliance

Disciplines: Mechanical

Location: Edmonton
Specialty: Ventilation & Air Quality

Paint Mixing Room Design and Modifications

Overview

An existing facility was flagged for non-compliance with the safety codes governing the spray application of combustible and flammable materials.

Project Goals

To support the facility to meet the standards of the NFPA 33 and NFPA 30 codes related to the spray application of flammable and combustible materials as there was no fire suppression system and no make-up air system in the space.

Our Solutions

Minimized air flow in the space to meet the 25% lower flammability limits and threshold values for safe operation without the risk of adverse health reactions.

Based on our calculations, reduced the size of the existing exhaust fan in the paint mixing the room and installed a ducted make-up air system with an electric heater and booster fan which was interlocked with the exhaust fan to prevent any back drafting of flue gases from natural gas equipment in the area. The make-up air was then passed air was through an UL 900 approved fiberglass filter pad prior to supply into the mixing room.

Worked with the owner to identify and install a pre-engineered dry chemical system for fire suppression. The fire suppression system was furnished with a 21 lb tank of dry chemical, a fire alarm control unit, an audible alarm, a manual pull station and heat detector to flood the room in case of an event.

Results

The paint mixing facility met the safety codes and was able to reopen and the staff were now working in a safer work space, no longer at risk of inhaling noxious gases.

References: NFPA 33, NFPA 30, NFPA 91, NFPA 10, National Fire Code. AB Building Code, ACGIH Industrial Ventilation Manual, Perry's Chemical Engineering Handbook